Electrical Conductor Sizing and Common Cable Types
A practical guide to conductor cross-sections, indicative current ratings and cable designations, with tables based on ČSN 33 2000-5-52.
When designing and installing electrical wiring, it is important to choose the right conductor or cable type and size. This choice affects the safety, service life and performance of the installation. Below you will find key values and conductor designations based on applicable standards.
The values below are for guidance and are based on ČSN 33 2000-5-52, which provides current-carrying capacities for electrical wiring according to the wiring type and installation method.

Permissible currents for copper conductors (cables) with PVC insulation
The permissible current depends on the conductor cross-section, insulation type and installation method. The table below gives indicative permissible currents for PVC-insulated copper conductors by installation method.
The table applies at a conductor temperature of 70°C, ambient air temperature of 30°C and ground temperature of 20°C. Values are indicative only.
| Conductor cross-section [mm²] | Copper core diameter [mm] | In an insulated wall, in conduit or directly [A] | In conduit on a wall [A] | Cable directly on a wall, ceiling or floor [A] | Cable directly buried in the ground [A] |
|---|---|---|---|---|---|
| 1 | 1.12 | 10.5 | 12 | 13.5 | 23 |
| 1.5 | 1.4 | 13 | 15.5 | 17.5 | 28 |
| 2.5 | 1.8 | 18 | 21 | 24 | 38 |
| 4 | 2.24 | 24 | 28 | 32 | 48 |
| 6 | 2.8 | 31 | 36 | 41 | 61 |
| 10 | 3.55 | 42 | 50 | 57 | 81 |
| 16 | 4.5 | 56 | 68 | 76 | 105 |
| 25 | 5.6 | 73 | 89 | 96 | 134 |
| 35 | 6.7 | 89 | 111 | 119 | 161 |
| 50 | 8 | 108 | 134 | 144 | 191 |
| 70 | 9.5 | 136 | 171 | 184 | 236 |
| 95 | 11 | 164 | 207 | 223 | 280 |
| 120 | 12.4 | 188 | 239 | 259 | 317 |
| 150 | 13.8 | 216 | 294 | 359 | |
| 185 | 15.4 | 248 | 341 | 401 | |
| 240 | 17.5 | 286 | 403 | 464 | |
| 300 | 19.6 | 329 | 464 | 525 |
Indicative rated currents for selected conductor and cable types
Conductors must be sized not only according to their rated current, but also according to cable length (voltage drop), short-circuit parameters and cooling conditions.
Values are indicative only.
| Conductor cross-section [mm²] | Copper core diameter [mm] | H05V-U (CY) [A] single-core | H05VV-F (CYSY) [A] 3-core | H05RR-F (CGSG) [A] 3-core | H05RN-F (CGTGU) [A] 3-core |
|---|---|---|---|---|---|
| 0.75 | 0.97 | 16 | 14.5 | 10.5 | |
| 1 | 1.12 | 19 | 17 | 12.5 | |
| 1.5 | 1.4 | 25 | 21 | 16 | 15.5 |
| 2.5 | 1.8 | 33 | 29 | 21 | 21 |
| 4 | 2.24 | 45 | 39 | 29 | 28 |
| 6 | 2.8 | 58 | 37 | 36 | |
| 10 | 3.55 | 81 | 50 | 49 | |
| 16 | 4.5 | 109 | 69 | 67 | |
| 25 | 5.6 | 146 | 87 | ||
| 35 | 6.7 | 181 | 109 | ||
| 50 | 8 | 219 | 142 | ||
| 70 | 9.5 | 281 | 170 | ||
| 95 | 11 | 341 | 205 |
ČSN/CENELEC designation conversion table
| ČSN / former designation | CENELEC / harmonised designation | Use / note |
|---|---|---|
| CY | H05V-U / H07V-U | Single-core solid conductor for conduit |
| CYA | H05V-K / H07V-K | Single-core stranded conductor for trunking and enclosures |
| CYKY | NYM | Fixed power cable for indoor and some outdoor installations |
| CYLY | H03VV-F / H05VV-F | Flexible PVC cord with stranded cores for appliances |
| CYKYLo | NYIF / NYM-O,J (flat) | Fixed flat cable with solid cores for installation under plaster |
| CYSY | H05VV-F | Flexible cable for equipment and appliances |
| CGSG | H05RR-F | Light-duty rubber cable for portable appliances |
| CGTG | H07RN-F | Rubber cable for demanding conditions and outdoor use |
| O | H03VV-F | Light-duty flexible cable (2 cores), for example for luminaires |
| OY | H05VV-F | Light-duty PVC appliance cable (3–5 cores) |
| OZ | H05VV5-F | Screened cable for control systems and equipment |
| SYKFY | J-YY | Fixed communication cable for low-voltage signals |
| J-Y(St)Y | J-Y(St)Y | Screened communication cable, for example for security systems |
CENELEC harmonised cable designations follow a defined structure. Each position conveys specific information.
Designation structure
| Position | Meaning | Examples / options |
|---|---|---|
| 1 | Standard type |
|
| 2–3 | Rated voltage |
|
| 4 | Insulation type |
|
| 5 | Sheath or additional insulation type |
|
| 6 | Conductor construction |
|
Designation examples:
- H05VV-F = harmonised, 300/500 V, PVC insulation, PVC sheath, flexible stranded conductor
- H07RN-F = harmonised, 450/750 V, rubber insulation, neoprene sheath, flexible conductor
- H05V-K = harmonised, 300/500 V, PVC insulation, no outer sheath, stranded conductor
Recommendations
- Always follow the current version of ČSN 33 2000-5-52, Low-voltage electrical installations – Part 5-52: Selection and erection of electrical equipment – Wiring systems.
- For longer cable runs, take voltage drop into account.
- For outdoor and underground installation, consider the cooling conditions.
This article provides indicative information. Final sizing should always be based on the project documentation and applicable technical standards.