Electrical Conductor Sizing and Common Cable Types

Electrical Conductor Sizing and Common Cable Types

A practical guide to conductor cross-sections, indicative current ratings and cable designations, with tables based on ČSN 33 2000-5-52.

When designing and installing electrical wiring, it is important to choose the right conductor or cable type and size. This choice affects the safety, service life and performance of the installation. Below you will find key values and conductor designations based on applicable standards.

The values below are for guidance and are based on ČSN 33 2000-5-52, which provides current-carrying capacities for electrical wiring according to the wiring type and installation method.

Permissible currents for copper conductors (cables) with PVC insulation

The permissible current depends on the conductor cross-section, insulation type and installation method. The table below gives indicative permissible currents for PVC-insulated copper conductors by installation method.

The table applies at a conductor temperature of 70°C, ambient air temperature of 30°C and ground temperature of 20°C. Values are indicative only.

Permissible currents for copper conductors (cables) with PVC insulation

Conductor cross-section [mm²]Copper core diameter [mm]In an insulated wall, in conduit or directly [A]In conduit on a wall [A]Cable directly on a wall, ceiling or floor [A]Cable directly buried in the ground [A]
11.1210.51213.523
1.51.41315.517.528
2.51.818212438
42.2424283248
62.831364161
103.5542505781
164.5566876105
255.6738996134
356.789111119161
508108134144191
709.5136171184236
9511164207223280
12012.4188239259317
15013.8216294359
18515.4248341401
24017.5286403464
30019.6329464525

Indicative rated currents for selected conductor and cable types

Conductors must be sized not only according to their rated current, but also according to cable length (voltage drop), short-circuit parameters and cooling conditions.

Values are indicative only.

Indicative rated currents for selected conductor and cable types

Conductor cross-section [mm²]Copper core diameter [mm]

H05V-U (CY) [A]

single-core

H05VV-F (CYSY) [A]

3-core

H05RR-F (CGSG) [A]

3-core

H05RN-F (CGTGU) [A]

3-core

0.750.971614.510.5
11.12191712.5
1.51.425211615.5
2.51.833292121
42.2445392928
62.8583736
103.55815049
164.51096967
255.614687
356.7181109
508219142
709.5281170
9511341205

ČSN/CENELEC designation conversion table

ČSN/CENELEC designation conversion table
ČSN / former designationCENELEC / harmonised designationUse / note
CYH05V-U / H07V-USingle-core solid conductor for conduit
CYAH05V-K / H07V-KSingle-core stranded conductor for trunking and enclosures
CYKYNYMFixed power cable for indoor and some outdoor installations
CYLYH03VV-F / H05VV-FFlexible PVC cord with stranded cores for appliances
CYKYLoNYIF / NYM-O,J (flat)Fixed flat cable with solid cores for installation under plaster
CYSYH05VV-FFlexible cable for equipment and appliances
CGSGH05RR-FLight-duty rubber cable for portable appliances
CGTGH07RN-FRubber cable for demanding conditions and outdoor use
OH03VV-FLight-duty flexible cable (2 cores), for example for luminaires
OYH05VV-FLight-duty PVC appliance cable (3–5 cores)
OZH05VV5-FScreened cable for control systems and equipment
SYKFYJ-YYFixed communication cable for low-voltage signals
J-Y(St)YJ-Y(St)YScreened communication cable, for example for security systems

CENELEC harmonised cable designations follow a defined structure. Each position conveys specific information.

Designation structure
Designation structure
PositionMeaningExamples / options
1Standard type
  • H = harmonised according to an HD standard
2–3Rated voltage
  • 03 = 300/300 V,
  • 05 = 300/500 V,
  • 07 = 450/750 V,
  • 1 = 600/1000 V
4Insulation type
  • V = PVC,
  • R = rubber,
  • G = thermoplastic,
  • Z = halogen-free
5Sheath or additional insulation type
  • V = PVC,
  • R = rubber,
  • N = neoprene,
  • Z = halogen-free
6Conductor construction
  • U = solid,
  • K = stranded,
  • F = flexible multicore

Designation examples:
  • H05VV-F = harmonised, 300/500 V, PVC insulation, PVC sheath, flexible stranded conductor
  • H07RN-F = harmonised, 450/750 V, rubber insulation, neoprene sheath, flexible conductor
  • H05V-K = harmonised, 300/500 V, PVC insulation, no outer sheath, stranded conductor

Recommendations

  • Always follow the current version of ČSN 33 2000-5-52, Low-voltage electrical installations – Part 5-52: Selection and erection of electrical equipment – Wiring systems.
  • For longer cable runs, take voltage drop into account.
  • For outdoor and underground installation, consider the cooling conditions.

This article provides indicative information. Final sizing should always be based on the project documentation and applicable technical standards.