EG.D connection requirements effective from 1 January 2025
The distribution company EG.D has issued new connection requirements.

The changes to the EG.D requirements mainly affect enclosures for electricity sharing:
- All references and requirements related to TT networks have been removed from the connection requirements.
- A note has been added to section 1 stating that earthing associated with a building’s electrical installation must not be considered or installed in the cable service connection box.
- Section 10.6 introduces a new requirement for the OR control relay: it must not have a manual switching function, including a test button.
- Section 13, on temporary supplies, now states that site and other portable electricity meter enclosures do not require an installation switch.
- Section 17 on electricity sharing has been substantially revised. Many requirements have been removed, and the connection requirements now include provisions previously contained in a separate document, More detailed requirements for preparing a consumption point for electricity sharing. We covered these requirements here.
- Section 17.1.1 retains, in particular, the requirement for a bath-style meter compartment without a cover panel.
- New sections 17.1.2 and 17.1.3 cover preparing the enclosure when switching to interval metering, including temporary connection of the existing non-interval meter.
- Section 19, which contains the wiring diagrams, has also changed. Diagrams 1 and 2 have been updated. Installation switches have been added to diagram 14 for connecting multiple meters in an apartment building. Diagrams 20 and 21 for TT networks have been removed. Unfortunately, the new requirements still show 1 July 2024 as the effective date for diagram 16, although EG.D postponed its effective date to 1 July 2025. More about the postponement here.
- The table of applicability of the connection requirements in section 21 has been revised to reflect electricity-sharing requirements. Existing installations are accepted, except that a cover panel over the meter is not permitted (see 17.1.1). For Metering on request / Consumption under control, the existing main circuit breaker is also accepted if it matches the contract.
...and more.
The changes mainly remove requirements for TT networks in EG.D’s rules and address electricity sharing and the preparation of enclosures for sharing.
The new connection requirements are effective from 1 January 2025.
The EG.D connection requirements can be downloaded here: EG.D connection requirements
(Document: Requirements for metering equipment at customers and small generating facilities connected to the LV network — effective from 1 January 2025)
Our enclosures always meet all requirements and changes to the connection conditions. See our range of enclosures suitable for EG.D here.

We are still expecting changes to ČEZ Distribuce’s connection requirements, so follow our website or subscribe to our news. Simply enter your email in the “Stay up to date” box below.